Features:
Specifications | ||
Maximum voltage between any terminal and earth ground | 600 V | |
Surge protection | 6 kV peak per IEC 61010-1 600 VCAT III, Pollution Degree 2 | |
Fuse for A input | 11 A, 1000 V FAST Fuse (Fluke PN 803293) | |
Display | Digital: 6,000 counts, updates 4 per second | |
Bar graph | 33 segments, updates 32 per second | |
Operating temperature | -10 °C to + 50 °C | |
Storage temperature | -40 °C to + 60 °C | |
Battery type | 9 volt Alkaline, NEDA 1604A/ IEC 6LR61 | |
Battery life | 400 hours typical, without backlight | |
Accuracy Specifications | ||
DC millivolts | Range/Resolution | 600.0 mV / 0.1 mV |
Accuracy | ± ([% of reading] + [counts]): 0.5% + 2 | |
DC volts | Range/Resolution | 6.000 V / 0.001 V 60.00 V / 0.01 V 600.00 V / 0.1 V |
Accuracy | ± ([% of reading] + [counts]): 0.5% + 2 | |
Auto volts | Range/Resolution | 600.0 V / 0.1 V |
Accuracy | 2.0 % + 3 (dc, 45 Hz to 500 Hz) 4.0 % + 3 (500 Hz to 1 kHz) |
|
AC millivolts¹ true-rms | Range/Resolution | 600.0 mV / 0.1 mV |
Accuracy | 1.0 % + 3 (dc, 45 Hz to 500 Hz) 2.0 % + 3 (500 Hz to 1 kHz) |
|
AC volts¹ true-rms | Range/Resolution | 6.000 V / 0.001 V 60.00 V / 0.01 V 600.0 V / 0.1 V |
Accuracy | 1.0 % + 3 (dc, 45 Hz to 500 Hz) 2.0 % + 3 (500 Hz to 1 kHz) |
|
Continuity | Range/Resolution | 600 Ω / 1 Ω |
Accuracy | Beeper on < 20 Ω, off > 250 Ω; detects opens or shorts of 500 μs or longer. |
|
Ohms | Range/Resolution | 600.0 Ω / 0.1 Ω 6.000 kΩ / 0.001 kΩ 60.00 kΩ / 0.01 kΩ 600.0 kΩ / 0.1 kΩ 6.000 MΩ / 0.001 MΩ |
Accuracy | 0.9 % + 1 | |
Range/Resolution | 40.00 MΩ / 0.01 MΩ | |
Accuracy | 5 % + 2 | |
Diode test | Range/Resolution | 2.00 V / 0.001 V |
Accuracy | 0.9% + 2 | |
Capacitance | Range/Resolution | 1000 nF / 1 nF 10.00 μF / 0.01 μF 100.0 μF / 0.1 μF 9999 μF / 1 μF 100 μF to 1000 μF |
Accuracy | 1.9% + 2 | |
Range/Resolution | > 1000 μF | |
Accuracy | 5% + 20% | |
Lo-Z capacitance | Range | 1 nF to 500 μF |
Accuracy | 10% + 2 typical | |
AC amps true-rms (45 Hz to 500 Hz) | Range/Resolution | 6.000 A / 0.1 A 10.00 A / 0.01 A |
Accuracy | 1.5% + 3 20 A continuous overload for 30 seconds max |
|
DC amps | Range/Resolution | 6.000 A / 0.1 A10.00 A / 0.01 A |
Accuracy | 1.0% + 3 20 A continuous overload for 30 seconds max |
|
Hz (V or A input)² | Range/Resolution | 99.99 Hz / 0.01 Hz 999.99 Hz / 0.1 Hz 9.999 Hz / 0.001 Hz 50.00 Hz / 0.01 Hz |
Accuracy | 0.1% + 2 |