Your shopping cart is empty!

Availability: กรุณาสอบถามค่ะ
testo 435-4 multi-function measuring instrument with built-in differential pressure measurement for air conditioning, ventilation and Indoor Air Quality, with data memory, PC software and USB data transfer cable, includes battery and calibration protocol
This measuring instrument needs a probe for being commissioned.
Product description
The ambient air conditions measuring instrument, for asssessing Indoor Air Quality and tuning and testing VAC systems, stands out on account of its efficient measurement process.
The user-friendly measuring instrument has the right measurement engineering for every application and different flow speeds; for example, thermal probes, vane or Pitot tube measurement.
Probe-controlled menus and selectable user profiles, e.g. for duct measurement or long-term measurement, ensure the user-friendliest operation possible.
The new IAQ probe measures Indoor Air Quality by measuring the CO2 level, air moisture and air temperature. In addition, lux and comfort level probes can be connected to measure draught air. Clear analysis and archiving ensure convenient documentation.
Temperature and humidity measurement is built-in in the new thermal probe. The special flow protocol professionally documents duct measurements.
It is also possible to connect additional temperature and humidity probes. Readings from up to 3 temperature or humidity probes can be displayed in the measuring instrument; data transmission is by radio, i.e. wireless.
Technical data |
|
---|---|
Storage temperature |
-30 to +70 °C |
Operating temperature |
-20 to +50 °C |
Battery type |
Alkali manganese, mignon, Type AA |
Battery life |
200 h (typical vane measurement) |
Dimensions |
225 x 74 x 46 mm |
Housing material |
ABS/TPE/Metal |
Typ T (Cu-CuNi)
Technical data |
|
---|---|
Measuring range |
-200 to +400 °C |
Accuracy |
±0.3 °C (-60 to +60 °C) ±(0.2 °C + 0.5% of mv) (remaining range) |
Resolution |
0.1 °C |
Differential pressure
Technical data |
|
---|---|
Measuring range |
0 to +25 hPa |
Accuracy |
±0.02 hPa (0 to +2 hPa) |
Resolution |
0.01 hPa |
Overload |
200 hPa |
NTC
Technical data |
|
---|---|
Measuring range |
-50 to +150 °C |
Accuracy |
±0.2 °C (-25 to +74.9 °C) |
Resolution |
0.1 °C |
Absolute pressure probe
Technical data |
|
---|---|
Measuring range |
0 to+2000 hPa |
Resolution |
0.1 hPa |
Lux
Technical data |
|
---|---|
Measuring range |
0 to +100000 Lux |
Resolution |
1 Lux; 0.1 Hz |
Hot Wire
Technical data |
|
---|---|
Measuring range |
0 to +20 m/s |
Resolution |
0.01 m/s |
CO₂
Technical data |
|
---|---|
Measuring range |
0 to +10000 ppm CO2 |
Resolution |
1 ppm CO2 |
Typ K
Technical data |
|
---|---|
Measuring range |
-200 to +1370 °C |
Accuracy |
±0.3 °C (-60 to +60 °C) |
Resolution |
0.1 °C |
Vane
Technical data |
|
---|---|
Measuring range |
0 to +60 m/s |
Resolution |
0.01m/s (60 + 100 mm Vane) |
humid. sensor, cap.
Technical data |
|
---|---|
Measuring range |
0 to +100 %RH |
Resolution |
0.1 %RH |